BASIC INFO
Schneider ATV320U04M2C Variable Speed Drives ATV320 Altivar Machine
range of product |
Altivar Machine ATV320
|
|
---|---|---|
product or component type |
Variable speed drive
|
|
product specific application |
Complex machines
|
|
device short name |
ATV320
|
|
format of the control block |
Compact
|
|
product destination |
Synchronous motors
Asynchronous motors |
|
EMC filter |
Class C2 EMC filter integrated
|
|
IP degree of protection |
IP20 conforming to EN/IEC 61800-5-1
|
|
degree of protection |
UL type 1 with UL type 1 conformity kit
|
|
type of cooling |
Fanless
|
|
network number of phases |
1 phase
|
|
[Us] rated supply voltage |
200...240 V (- 15...10 %)
|
|
supply frequency |
50...60 Hz (- 5...5 %)
|
|
motor power kW |
0.37 kW for heavy duty
|
|
motor power hp |
0.5 hp for heavy duty
|
|
line current |
5.2 A at 200 V for heavy duty
4.3 A at 240 V for heavy duty |
|
prospective line Isc |
1 kA
|
|
apparent power |
1 kVA at 240 V for heavy duty
|
|
continuous output current |
3.3 A at 4 kHz for heavy duty
|
|
maximum transient current |
5 A during 60 s for heavy duty
|
|
asynchronous motor control profile |
Flux vector control without sensor, standard
Voltage/frequency ratio, 2 points Voltage/frequency ratio, 5 points Voltage/frequency ratio - Energy Saving, quadratic U/f Flux vector control without sensor - Energy Saving |
|
synchronous motor control profile |
Vector control without sensor
|
|
speed drive output frequency |
0.1...599 Hz
|
|
nominal switching frequency |
4 kHz
|
|
switching frequency |
4...16 kHz with current derating
2...16 kHz adjustable |
|
safety function |
STO (safe torque off) SIL 3
SS1 (safe stop 1) SMS (safe maximum speed) SLS (safe limited speed) GDL (guard door locking) |
|
communication port protocol |
Modbus
CANopen |
|
optional communication modules |
Communication module: CANopen daisy chain RJ45
Communication module: CANopen SUB-D 9 Communication module: CANopen open style terminal block Communication module: EtherCAT RJ45 Communication module: DeviceNet Communication module: Ethernet/IP Communication module: Profibus DP V1 Communication module: Profinet Communication module: Ethernet Powerlink |
variant |
Standard version
|
|
---|---|---|
output voltage |
<= power supply voltage
|
|
permissible temporary current boost |
1.5 x In during 60 s for heavy duty
|
|
speed range |
1...100 with asynchronous motor in open-loop mode
|
|
speed accuracy |
+/- 10 % of nominal slip 0.2 Tn to Tn
|
|
torque accuracy |
+/- 15 %
|
|
transient overtorque |
170...200 % of nominal motor torque
|
|
braking torque |
<= 170 % with braking resistor during 60 s
|
|
regulation loop |
Adjustable PID regulator
|
|
motor slip compensation |
Adjustable 0...300 %
Automatic whatever the load Not available in voltage/frequency ratio (2 or 5 points) |
|
acceleration and deceleration ramps |
S
Ramp switching CUS Deceleration ramp adaptation U Deceleration ramp automatic stop DC injection Linear |
|
braking to standstill |
By DC injection
|
|
protection type |
Drive: thermal protection
Drive: overcurrent between output phases and earth Drive: input phase breaks Drive: overheating protection Drive: short-circuit between motor phases |
|
frequency resolution |
Display unit: 0.1 Hz
Analog input: 0.012/50 Hz |
|
electrical connection |
Control, screw terminal: 0.5...1.5 mm² AWG 20...AWG 16
Motor/braking resistor, screw terminal: 2.5...4 mm² AWG 14...AWG 12 Power supply, screw terminal: 2.5...4 mm² AWG 14...AWG 12 |
|
connector type |
1 RJ45 for Modbus/CANopen on control terminal
|
|
physical interface |
2-wire RS 485 for Modbus
|
|
transmission frame |
RTU for Modbus
|
|
transmission rate |
4.8, 9.6, 19.2, 38.4 kbit/s for Modbus
50 kbps, 125 kbps, 250 kbps, 500 kbps, 1 Mbps for CANopen |
|
data format |
8 bits, configurable odd, even or no parity for Modbus
|
|
type of polarization |
No impedance for Modbus
|
|
number of addresses |
1...247 for Modbus
1...127 for CANopen |
|
method of access |
Slave for CANopen
|
|
supply |
Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC (+/- 5 %) current <= 10 mA (overload and short-circuit protection)
|
|
local signalling |
1 LED green for CANopen run
1 LED red for CANopen error 1 LED red for drive fault |
|
width |
72 mm
|
|
height |
143 mm
188 mm with EMC plate |
|
depth |
138 mm
|
|
product weight |
1 kg
|
|
analogue input number |
3
|
|
analogue input type |
Voltage (AI1): 0...10 V DC, impedance 30000 Ohm, resolution 10 bits
Bipolar differential voltage (AI2): +/- 10 V DC, impedance 30000 Ohm, resolution 10 bits Current (AI3): 0...20 mA (or 4-20 mA, x-20 mA, 20-x mA or other patterns by configuration), impedance 250 Ohm, resolution 10 bits |
|
discrete input number |
7
|
|
discrete input type |
Programmable (sink/source) (DI1...DI4): 24...30 V DC: level 1 PLC
Programmable as pulse input 20 kpps (DI5): 24...30 V DC: level 1 PLC Switch-configurable PTC probe (DI6): 24...30 V DC Safe torque off (STO): 24...30 V DC, impedance 1500 Ohm |
|
discrete input logic |
Negative logic (sink): : DI1...DI6, > 19 V (state 0) < 13 V (state 1)
Positive logic (source): : DI1...DI6, < 5 V (state 0) > 11 V (state 1) |
|
analogue output number |
1
|
|
analogue output type |
Software-configurable current (AQ1): 0...20 mA, impedance 800 Ohm, resolution 10 bits
Software-configurable voltage (AQ1): 0...10 V, impedance 470 Ohm, resolution 10 bits |
|
sampling duration |
Analog input (AI1, AI2, AI3): 2 ms
Analog output (AQ1): 2 ms |
|
accuracy |
Analog input AI1, AI2, AI3: +/- 0.2 % for a temperature of -10...60 °C
Analog input AI1, AI2, AI3: +/- 0.5 % for a temperature of 25 °C Analog output AQ1: +/- 1 % for a temperature of 25 °C Analog output AQ1: +/- 2 % for a temperature of -10...60 °C |
|
linearity error |
Analog input (AI1, AI2, AI3): +/- 0.2...0.5 % of maximum value
Analog output (AQ1): +/- 0.3 % |
|
discrete output number |
3
|
|
discrete output type |
Configurable relay logic NO/NC (R1A, R1B, R1C): electrical durability 100000 cycles
Configurable relay logic NO (R2A, R2B): electrical durability 100000 cycles Logic (LO) |
|
refresh time |
Logic input (DI1...DI6): 8 ms (+/- 0.7 ms)
Relay output (R1A, R1B, R1C): 2 ms Relay output (R2A, R2C): 2 ms |
|
minimum switching current |
Relay output (R1, R2): 5 mA at 24 V DC
|
|
maximum switching current |
Relay output (R1) on resistive load (cos phi = 1: 3 A at 250 V AC
Relay output (R1) on resistive load (cos phi = 1: 4 A at 30 V DC Relay output (R1, R2) on inductive load (cos phi = 0.4: 2 A at 250 V AC Relay output (R1, R2) on inductive load (cos phi = 0.4: 2 A at 30 V DC Relay output (R2) on resistive load (cos phi = 1: 5 A at 250 V AC Relay output (R2) on resistive load (cos phi = 1: 5 A at 30 V DC |
|
specific application |
Machinery
|
|
Variable speed drive application selection |
Hoisting self erecting
Material handling carousel Material handling conveyor Material handling lifting platfrom Material handling palletizers - medium performance Material handling transfer table Material handling turn table Material working (wood, ceramic, stone, pvc, metal) cutting - medium accuracy Material working (wood, ceramic, stone, pvc, metal) drilling Material working (wood, ceramic, stone, pvc, metal) saw Packaging bagging Packaging feed conveyor low performance Packaging filling bottles - intermittent operation Packaging linear labeling Packaging other application Packaging stretching wrapping Packaging tray take Textile knitting Textile printing machines Textile spinning Washing machines car Washing machines other application Hoisting standard crane - travelling or trolley |
|
Motor power range |
0...0.5 kW 200...240 V 1 phase
|
|
motor starter type |
Variable speed drive
|
isolation |
Between power and control terminals
|
|
---|---|---|
insulation resistance |
> 1 mOhm at 500 V DC for 1 minute to earth
|
|
power dissipation in W |
32.2 W (fanless) at 200 V, 4 kHz
|
|
operating position |
Vertical +/- 10 degree
|
|
electromagnetic compatibility |
Conducted radio-frequency immunity test conforming to IEC 61000-4-6 level 3
Electrical fast transient/burst immunity test conforming to IEC 61000-4-4 level 4 Electrostatic discharge immunity test conforming to IEC 61000-4-2 level 3 Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3 level 3 Voltage dips and interruptions immunity test conforming to IEC 61000-4-11 1.2/50 µs - 8/20 µs surge immunity test conforming to IEC 61000-4-5 level 3 |
|
pollution degree |
2 conforming to EN/IEC 61800-5-1
|
|
vibration resistance |
1.5 mm peak to peak (f = 2...13 Hz) conforming to EN/IEC 60068-2-6
1 gn (f = 13...200 Hz) conforming to EN/IEC 60068-2-6 |
|
shock resistance |
15 gn during 11 ms conforming to EN/IEC 60068-2-27
|
|
relative humidity |
5...95 % without condensation conforming to IEC 60068-2-3
5...95 % without dripping water conforming to IEC 60068-2-3 |
|
ambient air temperature for operation |
-10...50 °C without derating
50...60 °C with derating factor |
|
ambient air temperature for storage |
-25...70 °C
|
|
operating altitude |
<= 1000 m without derating
1000...3000 m with current derating 1 % per 100 m |
|
standards |
EN/IEC 61800-3
EN/IEC 61800-3 environment 1 category C2 EN/IEC 61800-5-1 IEC 60721-3 IEC 61508 IEC 13849-1 |
|
product certifications |
RCM
UL NOM 117 EAC CSA |
|
marking |
CE
|
Sustainable offer status |
Green Premium product
|
|
---|---|---|
RoHS (date code: YYWW) | ||
REACh | ||
Product environmental profile | ||
Product end of life instructions |
We are specialized in intelligent instruments, including : control system, transmitters, flow meters,sensors, recorders, analyzers, control valves, controllers, PLC's, etc.
We mainly supply Yokogawa ,Honeywell,Siemens,ABB,FLUKE,Endress+Hauser,Schneider Electric,Moeller,FUJI,Omron,Pepperl+Fuchs,Hima,Yaskawa, Norgren, Hach, Weidmuller ,Phoenix,MTL,Testo etc.
Why choose us?
1. 100% original product, 100% quality assurance.
If you find a fake. Please contact us without hesitation! We afford the shipment cost! We send you a new product asking zero cent!
2. Varied payment methods.
We adopt T/T, western union and paypal. If you can not trust us , you can choose to pay it via Aliexpress! 100% make your money safe!
3.SHIPPING:
We can shipping all over the world.via DHL,UPS,Fedex,TNT and EMS etc., the packaging is very safe and strong. if you have any special needs,please notify me.
It will take 3 to 7days to reach in your hands.
Packaging:
Imported with original packaging or standard export packing.Customize design is acceptable.
Contact:
HONGKONG XIEYUAN TECH CO., LIMITED
Email:becky@hkxytech.com Web:www.hkxytech.com
Mobile:+86-15972186287(Whatsapp & Wechat)